top of page
  • Facebook
  • Twitter
  • Linkedin

DSPPA IP PAVA EVACUATION SYSTEM

The PAVA8000 is a fire emergency broadcast system that supports manual operation and timing programming functions, and is manually prioritized. It supports real-time detection of equipment operating status and operation log records. The broadcasting system can be used for fire emergency broadcasting, daily business broadcasting and background broadcasting.  The system is positioned as a small emergency broadcasting system, which is mainly used for small to medium sized shopping malls, office buildings and exhibition halls.

Compliant with " GB16806-2006  (FAS) " standard, EN 54 voice alarm system

Emergency broadcast can be made from PAVA8009 Fireman's Microphone  or amplifier,.

Can be remotely controlled from PC software, transmission distance no limitation without delay 

Backup amplifier for automatic Changeover and speaker line detection  for changeover.

PC software for speaker line real time monitoring

Screenshot%202020-09-10%20at%209.39_edit

VOICE EVACUATION CONTROLLER

PAVA 8500.  

8 zones speaker output(could be extended up to 1000 zones)

Built in 500W digital amplifier
One button alarm, built in EVAC message & Chime
8 Zones speaker output with individual volume control

Support remote Mic zones or group paging

DC battery backup monitoring
Real time monitor with EMC microphone for emergency situation avacuation

8 dry contact trigger input/output, DC24V override output
Support 100V Speaker AB line outputs with impedance supervision

Screenshot 2020-09-10 at 9.40.13 AM.png

16 ZonesPaging Station

PAVA8008/PAVA8008E

Voice evacuation system  paging Mic

Each microphone of 16  zones capacity

Zones extendable by expansion unit

System indicators of AC/DC, fault, Mic, etc.

Comply with EN54-16 requirements

Screenshot 2020-09-10 at 9.40.06 AM.png

Fireman Microphone

PAVA 8009

IP network terminal with built-in amplifier

4-8Ω speaker output
Built-in 2x25W digital amplifier
Audio source: AUX, Mic, USB, SD

EMC output and shortcut output

Wall mounted structure, conform to the EN standard

Programmable for the buttons
Microphone real-time monitoring
Support paging priority setting

Support AC220V/POE power supply
Long distance transmission(Dante technology)

Screenshot%202020-09-10%20at%209.51_edit

Touch Screen Paging Station

PAVA 6005

With 7" touch screen to operate and display working status

Paging key mode and PTT mode can be configured
Paging priority can be configured
Support zone/group paging through touch screen

Two RJ45 ports for connection
One 3.5mm line input for audio source
One 3.5mm output interface for monitor
Support DC 24V or phantom power 24V supply

Screenshot 2020-09-10 at 9.41.21 AM.png

FIRE PROOF SPEAKERS

EN 54 CERTIFIED

6W/10W SPEAKERS

The  mesh cover is fine aluminum mesh,  rust-proof and durable.
The  speaker’s  fireproof  cover  is made by punch forming of high-quality steel,  with flame-retardant sleeve joint, which can be sealed completely to prevent  fire.

The speaker has a reinforced adjustable clip, durable and reliable, convenient for installation, and also has a safety steel rope hook, so as to realize double protection.

EN 54 STANDARDS

The EN 54 Fire detection and fire alarm system 

EN 54 is a mandatory standard of European Union market that specifies requirements and laboratory test for every component of fire detection and fire alarm system.The standard is developed and approved by European Committee for Standardization (CEN). It came into force in April 2011. It has been widely recognized around the world. Three sections regarding to Voice Evacuation Systems in the standard:

EN 54-4: Power supply equipment
An uninterrupted monitored power supply system is crucial for this type of system, guaranteeing system availability at all times. Some of the characteristics that have to be fulfilled:

  • Monitoring and detecting faults in batteries

  • Protecting against surge

  • Protection against over discharge

EN 54-16: Voice alarm control and indicating equipment
Requirements that the control system must fulfill as well as the tests that have to be undertaken. Some of the characteristics that have to be fulfilled:

  • Immediate availability. It must be able to send warning message 10 seconds after applying electric power supply

  • Immediate response. Less than 3 seconds after an alarm is set off

  • Supervision of the critical signal route: the alarm system link, the PA system, th amplifiersand the loudspeaker

lines. This supervision must not interfere with the normal operation of the system and must be supervised at

least every 100 seconds

  • Status indication and fault monitoring

  • On some occasions a back-up amplifier is compulsory in case there is a problem with one of them

 

EN 54-24: Voice alarms - Loudspeakers
This establishes the requirements that must be fulfilled by the loudspeakers within emergency evacuation systems. Some of the characteristics that have to be fulfilled:

  • Ceramic connector to withstand high temperature● Thermal fuse

  • Fireproof dome

  • Fireproof cables

LEARN MORE